Service and diagnostics
18.11 Remote diagnostics
● Variable PingTransmissionInterval
Duration in seconds after which send is repeated,
e.g. PingTransmissionInterval = 15
● Variable PingServerPor
Port number of the Ping service with the manufacturer,
e.g. PingServerPort=6201
18.11.2
Remote diagnostics via Teleservice adapter IE at X127
The following settings must be made for remote diagnostics via modem using a Teleservice
adapter IE (TS Adapter) that is connected at X127.
Settings in the TS Adapter required
● IP address of the adapter: 192.168.215.30, subnet mask 255.255.255.224
● IP address of the caller: 192.168.215.29
These two addresses are also stored as standard in the "tcu.ini" file. If other addresses are
used, then appropriately change the entries "X127ModemIP" and "X127RemoteAccessIP"
in the "tcu.ini" file.
● Enable the ports for the services for S7 communication, http, HTTPS, SSH as well as VNC
(port 5900) in the firewall.
Connecting the modem for remote diagnostics
Figure 18-1
With the previously mentioned settings and the default values, in this configuration, remote
diagnostics via TS Adapter is possible without any additional changes having to be made.
454
Basic system with SINUMERIK Operate on NCU (and operating station with TCU)
Commissioning Manual, 12/2017, 6FC5397-1DP40-6BA1
SINUMERIK Operate (IM9)