Modbus Communication
3.3 Parameter Assignment/Addressing
Table 3-16
Network 2: Configure Parameters Menu (9916)
Parameter
ID
Modbus Baud Rate
9917
Modbus Parity
9947
Modbus Stop Bits
9948
Modbus Address
9920
Velocity Units
9924
Demand Scalar
9926
Aux Demand Scalar
9927
Network Timeout
9935
Table 3-17
Network 2: Register Data from Drive Menu (9500)
Parameter
Data From Drive 01
Data From Drive 02
Data From Drive 03 to 64
48
Unit
Default
Min
19200
None
1
1
1
%
1
-125
1
-125
0
0
ID
Unit
Default
9501
General Sta‐
tus
9502
Motor Speed
9503 to
None
9564
Max
Description
Set the Modbus network baud rate:
● 1200
● 2400
● 4800
● 9600
● 19200
Set the Modbus parity:
● none
● odd
● even
Set the Modbus stop bits:
● one
● two
247
Set the address of the node on the Modbus network.
Designate the units for velocity values from the drive:
● %
● RPM
● Hz
125
Set the scalar for input demand reference from the
network.
125
Set the auxiliary scalar for input demand reference
from the network.
65535
Set the timeout for network determined to be non-re‐
sponsive.
Min
Max
Description
Register data from drive parameter 1.
Register is not programmable.
Register data from drive parameter 2.
Register is not programmable.
Register data from drive parameters 3 to 64.
Registers are programmable.
NXGpro Communication
Function Manual, AB, A5E33486415A