ControlNet Communication
9.4 Planning/Configuring
9.4.7

Network Status (auto detect)

An SOP flag is available to show the network status:
● For network 1: Network1CommOk_I
● For network 2: Network2CommOk_I
The SOP flag is set to "1" (true) when the network connection is operating normally, and "0"
(false) when it is not operating normally.
The network status is automatically detected. Detection time takes approximately 20-40
milliseconds.
If a longer network timeout is desired for a network that automatically detects the network
status, it must be implemented through SOP logic.
9.4.8
Setup Example
Task
Set up network to indicate the following drive outputs on the PLC:
● general status
● motor speed
● output power
● number of active faults.
Procedure
Refer to Table
Address in Section Parameter Assignment/Addressing to establish whether an address or
register is changeable.
To indicate general status and motor speed:
1. The table shows that:
● 'Data from Drive 01' is not changeable; it is set to indicate general status. No action is
required.
● 'Data from Drive 02' is not changeable; it is set to indicate motor speed. No action is required.
To indicate output power:
1. The table shows that 'Data from Drive 03' is changeable, this can be set to indicate output
power.
2. Refer to Table
Address to determine that the corresponding parameter ID is 9403.
3. Enter parameter ID 9403.
4. Choose "output power" from the pick list.
The output power will be sent to the PLC using register 'Data from Drive 03'.
240
Correspondence between Drive Parameter ID and Communication Protocol
Correspondence between Drive Parameter ID and Communication Protocol