Fast Setup: Monitor Drive Status And Speed Feedback - Siemens SINAMICS PERFECT HARMONY GH180 Function Manual

Nxgpro communication medium-voltage variable frequency drive
Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

Table 5-19
Bit
Network1FixedRegBit0_I
Network1FixedRegBit1_I
Network1FixedRegBit2_I
Network1FixedRegBit3_I
Network1FixedRegBit4_I
Network1FixedRegBit5_I
Network1FixedRegBit6_I
Network1FixedRegBit7_I
Network1FixedRegBit8_I
Network1FixedRegBit9_I
Network1FixedRegBit10_I
Network1FixedRegBit11_I
Network1FixedRegBit12_I
Network1FixedRegBit13_I
Network1FixedRegBit14_I
Network1FixedRegBit15_I
Network1FixedRegBit3_I functions as a drive stop control bit only if parameter 'Start Stop Control'
1
(9945) is set to "Momentary". Otherwise this bit is reserved.
Note
To run the drive, the PLC must send 0x21 to register 'Data to Drive 01'. This hexadecimal value
sets bit 0 (run) and bit 5 (start/stop control from network).
To stop the drive, the PLC must send 0x08 or 0x00 to register 'Data to Drive 01'.
5.5.3

Fast Setup: Monitor drive status and speed feedback

To read status data from the drive, complete the following steps:
1. Set parameter 'Network 1 Type' (9901) to "Ethernet Modbus". This setup assumes that an
existing working TCP/IP network is established.
2. Verify the network settings for the parameters 'Subnet mask' (9961) and 'Gateway address'
(9962). The default subnet mask and gateway address work for most network
configurations.
3. Set parameter 'IP Address' (9960). The IP address must be unique to the drive.
NXGpro Communication
Function Manual, AB, A5E33486415A
Default definitions of Fixed Register Bits
Ethernet / IP Communication
5.5 Planning/Configuring
Default Definition
Run forward
Run reverse
Fault reset
Stop
1
Reserved
Start stop control from network
Speed commanded from network
Reserved for future assignment
127