Plc Setup Using Gsd Files; Network Setup Procedure - Siemens SINAMICS PERFECT HARMONY GH180 Function Manual

Nxgpro communication medium-voltage variable frequency drive
Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

6.4.5

PLC Setup using GSD files

A GSD file is a device description file in a specified format. The format must conform to the
Profibus™ Trade Organization (PTO) guidelines. Contact Siemens customer service for GSD
files.
Each device on the Profibus™ network must have a GSD file. The GSD file provides all relevant
data associated with a specific device for use by the configuration tool.
The GSD file provides an option for 136 bytes of input and output. If the configuration tool
cannot accommodate 136 bytes, the GSD file allows the choice of adding 8 or 16 bytes at a
time, until the correct quantity of input and output bytes are selected.
● To communicate with the drive, you must configure the Profibus™ master to have the same
quantity of bytes that are set by parameter 'Network 1 I/O Size' (9951) or 'Network 2 I/O
Size' (9952).
6.4.6

Network Setup Procedure

Note
Setup functions are contained in the Configure Parameters Menu (9902), which is a submenu
of the Communications Menu (9).
Access is security-controlled at level 7; you must enter the security code to access these
parameters.
Refer to the
and codes.
Use the following procedure to complete network setup. Refer to Table
Menu (9902) in Section Parameter Assignment/Addressing for the menus needed to complete
setup.
Procedure
1. Select a protocol using parameter 'Network 1 Type' (9901). Scroll to "Profibus" and press
[ENTER]. The Profibus™ configuration parameters are viewable.
2. Set parameter 'Profibus Address' (9904) to the desired network address for the drive.
3. Set parameter 'Velocity Units' (9080) to the desired motor speed units for motor
commanded speed and motor feedback speed scaling.
4. Where necessary, set parameter 'Demand Scalar' (9912) to:
n x commanded speed where –125 % to 125 %
5. Set parameter 'Aux Demand Scalar' (9913) if used.
NXGpro Communication
Function Manual, AB, A5E33486415A
NXGpro Control Operating Manual for further information on security access levels
Profibus Communication
6.4 Planning/Configuring
Configure Parameters
159