Modbus Ethernet Communication
4.4 Planning/Configuring
5. Next, set up the drive to correspond with the bits you want to use in the SOP. Refer to
Section
variable, and use the procedures detailed in this section to complete set up.
6. To enable speed settings from the network, add the following line to the SOP file:
RawDemandNetwork1_O =
See also
Software Programming (Page 77)
4.4.5
Network Interfaces
The NXGpro Control is equipped with a high performance 32-bit Ethernet chipset which is fully
compliant with IEEE 802.3 100 MBPS CSMA/CD standards.
● It uses a dedicated standard RJ-45 port located on the front of the CPU board that supports
Network 1.
● The Anybus™ Modbus™ Ethernet module uses a standard RJ-45 port located on the
module to support Network 2.
Possible configurations for Ethernet communication between an Modbus™ Ethernet device
and the NXGpro Control software are described below. Choose a configuration based on the
site infrastructure.
Direct Ethernet Connection
Direct connection is intended for a single Modbus™ Ethernet device that is connected to the
drive using an Ethernet crossover cable. This cable allows direct connection to the drive without
a hub or server.
Figure 4-3
The following hardware is required for this connection method:
● Crossover patch cable
● Coupler
96
Software Programming to find the bits and locate the associated keypad pick list
Direct Modbus Ethernet Communication Connection