ProfiDrive Communication
7.3 Planning/Configuring
7.3.3

Network Setup Procedure

Note
Setup functions are contained in the Configure Parameters Menu (9902), which is a submenu
of the Communications Menu (9).
Access is security-controlled at level 7; you must enter the security code to access these
parameters.
Refer to the
and codes.
Use the following procedure to complete network setup. Refer to Table
Menu (9902) in Section Parameter Assignment/Addressing for the menus needed to complete
setup.
Procedure
1. Select a protocol using parameter 'Network 1 Type' (9901). Scroll to "Profibus" and press
[ENTER]. The Profibus™ configuration parameters are viewable.
2. Set parameter 'Profibus Address' (9904) to the desired network address for the drive.
3. Set parameter 'Telegram Number' (9958) to the desired value for cyclic data use, using
one of the following options:
– 1
– 2
– 20
– 352
– 999
– 998
4. Use Table
Address in Section Parameter Assignment/Addressing to program the drive to send data
to and receive commands from the network. The table provides all available registers with
corresponding parameter ID.
5. Define the bits in the available registers using one of the following methods:
186
NXGpro Control Operating Manual for further information on security access levels
If the Telegram selected is 999 or 998 proceed to step 4, otherwise setup is complete.
Correspondence between Drive Parameter ID and Communication Protocol
Configure Parameters
NXGpro Communication
Function Manual, AB, A5E33486415A