Cell Status Data
Table B-20

Cell Status

Data ID
● 4030 (Phase A)
● 4040 (Phase B)
● 4050 (Phase C)
Note: When Medium Voltage is low, status of these registers is invalid.
Table B-21
Cell Bypass Status
Data ID
● 4060 (Phase A)
● 4070 (Phase B)
● 4080 (Phase C)
NXGpro Communication
Function Manual, AB, A5E33486415A
Bit
Description
0
Cell 1 status
1
2
Cell 2 status
3
4
Cell 3 status
5
6
Cell 4 status
7
8
Cell 5 status
9
10
Cell 6 status
11
12
Cell 7 status
13
14
Cell 8 status
15
Bit
Description
0
Cell 1 bypass status
1
2
Cell 2 bypass status
3
4
Cell 3 bypass status
5
6
Cell 4 bypass status
7
8
Cell 5 bypass status
9
10
Cell 6 bypass status
11
12
Cell 7 bypass status
13
14
Cell 8 bypass status
15
Output Data IDs
B.1 Output data IDs
Value
● 0 = Not installed
● 1 = Active
● 2 = Bypassed
● 3 = Faulted
Value
● 0 = Unavailable
● 1 = Bypassed
● 2 = Available