Table 5-12
Network 1: Register Data to Drive Menu (9600)
Parameter
Data To Drive Reg 01
Data To Drive Reg 02
Data To Drive Reg 03 to 64 9603 to
Network 2 Parameters
Table 5-13
Network 2: Configure Menu (9914)
Parameter
ID
Network 2 Type
9915
Table 5-14
Network 2: Configure Parameters Menu (9916)
Parameter
ID
Velocity Units
9924
Demand Scalar
9926
Aux Demand Scalar
9927
IP Address
9936
Subnet Mask
9937
Gateway Address
9938
NXGpro Communication
Function Manual, AB, A5E33486415A
ID
Unit
Default
9601
Fixed Reg
Bits
9602
Velocity De‐
mand
None
9664
Unit
Default
Min
None
Unit
Default
1
1
172.16.20.17
255.255.0.0
172.17.1.1
5.4 Parameter Assignment/Addressing
Min
Max
Description
Register data to drive parameter 1.
Register is not programmable.
Register data to drive parameter 2.
Register is not programmable.
Register data to drive parameters 3 to 64.
Registers are programmable.
Max Description
Designate the type of external network connected to the
drive:
● None
● Modbus
● DeviceNet
● Profibus
● Ethernet Modbus
● ControlNet
● Ethernet I/P
Min
Max
Description
Designate the units for velocity values
from the drive:
● %
● RPM
● Hz
-125
125
Set the scalar for input demand reference
from the network.
-125
125
Set the auxiliary scalar for input demand
reference from the network.
Set the system TCP/IP address.
Set the system TCP/IP subnet mask.
Set the system TCP/IP gateway address.
Ethernet / IP Communication
119