Figure 4-4 Network Modbus™ Ethernet Communication Connection - Siemens SINAMICS PERFECT HARMONY GH180 Function Manual

Nxgpro communication medium-voltage variable frequency drive
Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

Multiple Drive LAN Ethernet Connection
To use the LAN connection to control one or more drives on an existing network complete the
following steps:
● Assign a unique IP address to each drive.
● Set the menu items of the TCP/IP Setup Menu (9300) for each drive.
● For Network 1, set the following menu items based on the settings unique to the network.
Verify the network settings for the parameters 'IP Address", 'Subnet Mask' and 'Gateway
Address'. Refer to Tables titled Network 1: TCP/IP Setup Menu. and Network 1 : TCIP/IP
Setup Menu located in the previous section of this chapter to find the parameter numbers
for "IP Address', 'Subnet Mask' and the 'Gateway Address' based on the NXGpro software
version and hardware configuration.
● For Network 2, set the following menu items based on the settings unique to the network:
– IP Address (9336)
– Subnet Mask (9337)
– Gateway Address (9338)
Refer to Table
Assignment/Addressing of this chapter.
Figure 4-4
Network Modbus™ Ethernet Communication Connection
The following hardware is required for this connection method:
● EtherFast 10/100 hub
● Ethernet Cat5 cable
NXGpro Communication
Function Manual, AB, A5E33486415A
Network 2 Configure Parameters Menu (9916) in Section Parameter
Modbus Ethernet Communication
4.4 Planning/Configuring
97