Configuring Network Parameters - Siemens SINAMICS G120 Manual

Control of a g120 or g110m with an allen-bradley controller (compact/controllogix) via ethernet/ip
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

6 Configuring a Generic Ethernet Module
6.1.2

Configuring network parameters

Table 6-2 Configuring the Network Parameters
The module name should identify the
G120 to allow easy selection from
other modules configured in the
controller. It is also the name used for
the controller level tag that will hold
the data. Use the Description box to
describe the Drive objects contained
in the module.
The data exchange format should be
set to Integer (INT).
Enter the IP Address of the G120.
The Connection Parameters section
configures the IO Assemblies. The
Assembly Instances should always be
101 through 103 for the Input, Output
and Configuration Assembly
respectively. The size of the Input and
Output assemblies is the total number
of words. For Standard Telegram 1,
there are 2 words in and 2 words out.
For Telegram 352 there are 6 words
in and 6 words out.
In this example the speed block
telegram for T352 is shown.
SINAMICS G: Control of a G120 with an Allen-Bradley controller
(Compact/ ControlLogix with RSLogix 5000) via EtherNet/IP
Entry-ID: 82843076,
V4.0,
09/2018
26

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g110mSinamics g series

Table of Contents