Procedure
Refer to Table
Address in Section Parameter Assignment/Addressing to establish whether an address or
register is changeable.
General status and motor speed indication:
● 'Data from Drive 01' is not changeable; it is set to indicate general status. No action is
required.
● 'Data from Drive 02' is not changeable; it is set to indicate motor speed. No action is required.
Output power indication:
● Determine that the corresponding parameter ID is 9403 by referring to Table
Correspondence between Drive Parameter ID and Communication Protocol Address .
● Enter parameter ID 9403.
● Choose "output power" from the pick list. The output power will be sent to the PLC using
register 'Data from Drive 03'.
Number of active faults indication:
● 'Data from Drive 04' is changeable, this can be set to indicate the number of active faults.
● Determine that the corresponding parameter ID is 9404 by referring to Table
Correspondence between Drive Parameter ID and Communication Protocol Address .
● Enter parameter ID 9404.
– The pick list of data from drive variables appears. As "number of active faults" is not an
– Refer to Table
● Refer to Appendix
determine its data ID number (3000).
● Use arrow or number keys to enter 3000, and press [ENTER].
– The display now shows "ManId-3000".
– The number of active faults will be sent to the PLC using register 'Data from Drive 04'.
– If the data ID number is not found, the error message "Invalid Id Entered" is displayed.
Table 5-21
Completed Settings for Given Example
PLC Address or Register
Data from Drive 01 (not changeable)
Data from Drive 02 (not changeable)
Data from Drive 03
Data from Drive 04
NXGpro Communication
Function Manual, AB, A5E33486415A
Correspondence between Drive Parameter ID and Communication Protocol
'Data from Drive 03' is changeable, this can be set to indicate output power.
option in the pick list, you must specify it manually.
Data From Drive Pick List Variables in Section Parameter Assignment/
Addressing for a list of 'data from drive' pick list variables.
Output Data IDs and locate "number of active faults" in the tables to
Ensure that the data ID is correct.
Data
General status
Motor speed
Output power
Number of faults
Ethernet / IP Communication
5.5 Planning/Configuring
Scaling
16 bits
RPM
kW
0 to 128