Profibus Communication
6.1 Description
Rotary Switches
The rotary switches must both be set to 0, as shown in the following figure.
Figure 6-3
Status Indicators
The following figure shows the status indicators.
Figure 6-4
The table explains the status indicators.
Table 6-1
Status Indicator Descriptions
Status Indicator
Indication
(figure number)
1
Not used
2
On-line status
3
Off-line status
4
Fieldbus diagnos‐
tics
Termination Switch
The physical end nodes in a Profibus™ network must be terminated to avoid reflections on
the bus line. Use the termination switch on the module to terminate.
If the module is used at either of the physical ends of the network, the termination switch has
to be in the ON (down) position. In any other case, the switch must be in the OFF (up) position,
as shown in the following figure.
138
0
0
Rotary Switch Setting
Status Indicators
State
N/a
Off
Green
Off
Red
Off
Red, flashing at 1 Hz
Red, flashing at 2 Hz
Red, flashing at 4 Hz
Description
N/a
Module is not online.
Module is online on the fieldbus.
Module is not offline.
Module is offline from the fieldbus.
No diagnostics present.
Error in configuration: IN and/or OUT length set during initial‐
ization of the module is not equal to the length set during
configuration of the network.
Error in User Parameter data: the length/contents of the User
Parameter data set during initialization of the module is not
equal to the length/contents set during configuration of the
network.
Error in initialization of the Profibus™ communication ASIC.
NXGpro Communication
Function Manual, AB, A5E33486415A