Name
General Status
Motor Voltage
Total Current
Output Power
Motor Speed
Speed Demand
Speed Reference
Heartbeat
Drive State
Inp RMS Current
Input Frequency
Input Power Avg
Net1 Out Reg 1
Net1 Out Reg 2
Net1 Out Reg 3
NXGpro Communication
Function Manual, AB, A5E33486415A
Manual ID Unit
Scaling
2001
None
None
2100
Volts
/1
2190
Amps
/1
2230
KW
/1
2014
%
/10
RPM
/1
Hz
/10
2060
%
/100
2010
%
/100
2220
None
None
2210
None
None
2130
Amps
/1
2140
Hz
/100
2250
KW
/1
2002
None
None
2003
None
None
2004
None
None
5.4 Parameter Assignment/Addressing
16 Bit Data
Notes
Type
Bit Field
● Bit 0: Fault
● Bit 1: Alarm
● Bit 2: Running Forward
● Bit 3: Running Reverse
● Bit 4: Drive Ready
● Bit 5: Start/Stop Control From Network
● Bit 6: Speed Reference From Network
● Bit 7: At Speed Reference
● Bit 8: Speed In Percent
● Bit 9: Speed In RPM
● Bit 10: Speed In Hz
● Bit 11: Reserved for future use
● Bit 12: Reserved for future use
● Bit 13: Reserved for future use
● Bit 14: Reserved for future use
● Bit 15: Reserved for future use
Unsigned
Unsigned
Signed
Unsigned
Unsigned
Unsigned
Unsigned
1 count per millisecond
Unsigned
● 0 = Off
● 1 = Magnetizing
● 2 = Spinning Load
● 3 = Autotune
● 4 = Run
● 5 = Stop
● 6 = Coast
● 7 = Up Transfer
● 8 = Down Transfer
Unsigned
Unsigned
Unsigned
Bit Field
Network1Flag0_I - Network1Flag15_I
Bit Field
Network1Flag16_I - Network1Flag31_I
Bit Field
Network1Flag32_I - Network1Flag37_I
Ethernet / IP Communication
121