Ethernet / IP Communication

5.5 Planning/Configuring

5.5
Planning/Configuring
5.5.1

Overview: planning/configuring

This section describes the setup methods available for communication. The following topics
are explained:
● Fast setup procedures
● Network interfaces
● Network setup procedure
● Network status detection
● An example to illustrate the setup procedure.
Note
Fast setup procedures allow setup of a Network 1 interface with a minimum of detail.
5.5.2

Fast Setup: Control the drive using the default configuration

To control the drive using the default configuration, you must send commands to the drive's
'fixed reg bits' location. This location is register 'Data to Drive 01' as provided in Table
Correspondence between Drive Parameter ID and Communication Protocol Address in
Section
To control the drive from a PLC using the default configuration, complete the following steps.
1. Set parameter 'Network 1 Type' (9901) to "Ethernet Modbus". This setup assumes that an
existing working TCP/IP network is established.
2. Verify the network settings for the parameters 'Subnet Mask' and 'Gateway Address' . Refer
to Tables titled Network 1: TCP/IP Setup Menu. and Network 2: TCIP/IP Setup Menu
located in the previous section of this chapter to find the parameter numbers for the
'Gateway Address' and the 'Subnet Mask' based on the NXGpro software version and
hardware configuration.
3. Set parameter 'IP Address'. The IP address must be unique to the drive. Refer to Tables
titled Network 1: TCP/IP Setup Menu. and Network 2 : TCIP/IP Setup Menu located in the
previous section of this chapter to find the parameter number for the 'IP Address' based on
the NXGpro software version and hardware configuation.
4. Set parameter 'Net Control Type' (9944) to "Fixed". This sets the bits at register 'Data to
Drive 01' where the fixed register bits are located. The fixed register bits are interpreted as
shown in the following table.
5. Add the following line to the SOP:
Network1RunEnable_O = TRUE;
126
Parameter Assignment/Addressing .
NXGpro Communication
Function Manual, AB, A5E33486415A