F2: Analog Input Option; F3: Digital Input Option - YASKAWA GA800 Programming Manual

Ac drive for industrial applications
Table of Contents

Advertisement

No.
Name
(Hex.)
F1-51
PG-F3 PGoH Detection
Level
(03D3)
F1-52
Serial Encoder Comm
Speed
(03D4)

F2: Analog Input Option

No.
Name
(Hex.)
F2-01
Analog Input Function
Selection
(038F)
F2-02
Analog Input Option Card
Gain
(0368)
RUN
F2-03
Analog Input Option Card
Bias
(0369)
RUN

F3: Digital Input Option

No.
Name
(Hex.)
F3-01
Digital Input Function
Selection
(0390)
F3-03
Digital Input Data Length
Select
(03B9)
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Description
V/f
CL-V/f
OLV
CLV
AOLV
The drive will detect PGoH [Encoder (PG) Hardware Fault] if the value of this parameter
is smaller than the value of
Note:
This function is enabled when F1-20 = 1 [Encoder 1 PCB Disconnect Detect =
Enabled].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the communication speed between the PG-F3 option and the serial encoder.
0 : 1M/9600bps
1 : 500k/19200bps
2 : 1M/38400bps
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input method for the analog reference used with AI-A3.
0 : 3 Independent Channels
1 : 3 Channels Added Together
V/f
CL-V/f
OLV
CLV
AOLV
Sets the analog reference gain as a percentage when the maximum output frequency is
100%.
Note:
• Set F2-01 = 1 [Analog Input Function Selection = 3 Channels Added Together] to
enable this function.
• Parameter A1-02 [Control Method Selection] selects which parameter is the
maximum output frequency.
–A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
–A1-02 = 8: E9-02 [Maximum Speed]
V/f
CL-V/f
OLV
CLV
AOLV
Sets the analog reference bias as a percentage when the maximum output frequency is
100%.
Note:
• Set F2-01 = 1 [Analog Input Function Selection = 3 Channels Added Together] to
enable this function.
• Parameter A1-02 [Control Method Selection] selects which parameter is the
maximum output frequency.
–A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
–A1-02 = 8: E9-02 [Maximum Speed]
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the data format of digital input signals. This parameter is enabled when o1-03 = 0 or 1
[Frequency Display Unit Selection = 0.01 Hz or 0.01% (100% = E1-04)].
Note:
When o1-03 = 2 or 3 [Revolutions Per Minute (RPM) or User Units (o1-10 & o1-11)],
the input signal will be BCD. The o1-03 value sets the setting units.
0 : BCD, 1% units
1 : BCD, 0.1% units
2 : BCD, 0.01% units
3 : BCD, 1 Hz units
4 : BCD, 0.1 Hz units
5 : BCD, 0.01 Hz units
6 : BCD (5-digit), 0.02 Hz
7 : Binary input
8 : Multi-Function Digital Input
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of bits to set the frequency reference with DI-A3.
0 : 8-bit
1 : 12-bit
2 : 16-bit
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
.
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
1.9 F: Options
Default
Ref.
(Range)
80%
323
(1 - 100%)
0
323
(0 - 2)
Default
Ref.
(Range)
0
323
(0, 1)
100.0%
325
(-999.9 - +999.9%)
0.0%
325
(-999.9 - +999.9%)
Default
Ref.
(Range)
8
326
(0 - 8)
2
326
(0 - 2)
51
1

Advertisement

Table of Contents
loading

Table of Contents