Select UNDER TEMPERATURE:
[Main Menu > SETUP > (password) > ALARM SET > Temperature]
1> OVER TEMPERATURE
2> UNDER TEMPERATURE
PLEASE SELECT
5.
Use the arrow keys to set the battery minimum temperature alarm value, press Ent, and then Esc:
[Main Menu > SETUP > (password) > ALARM SET > Temperature > UNDER TEMPERATURE]
SET OVER TEMPERATURE ALARM VALUE
7.8.4
Setting Battery Integration Alarm
The Alarm Integration Factor determines the number of times that the controller polls and retries to
determine the UPS status before deciding on an error status. Setting the alarm integration factor too low will
cause spurious alarms to be generated; conversely, setting the alarm integration factor too high may result
in an alarm only being raised when it is already too late to take corrective action.
1.
Select INTEGRAT.:
[Main Menu > SETUP > (password) > ALARM SET]
1> AC VOLT
2> FLOAT VOLT
3> ---------
4> ---------
2.
Use the arrow keys to set the integration factor alarm value—press Ent to accept or Esc to
discard:
[Main Menu > SETUP > (password) > ALARM SET > INTEGRAT.]
SET INTEGRATION FACTOR
ENTER = ACCEPT
POWER +
UPS,
PARALLEL
USER GUIDE
G
E
AMATRONIC
LECTRONIC
Figure 134: Over/Under temperature menu
( 2 – 99) DEGREES
45
Figure 135: Set battery minimum temperature alarm
5> --------- 9>INTEGRAT.
6> ---------
7> TEMPERATURE
8> ---------
Figure 136: Alarm set menu
(1 – 30)
05
Figure 137: Set the integration factor alarm
,
. 2.0
REL
I
L
.
NDUSTRIES
TD
ESC = DISCARD