5. POWER + R
5.1
Start-up after Shutdown
This section describes the start-up procedures for the operator after a POWER + shutdown.
shutdown, the UPS on, Alarm and Load indicators will flash
After a normal POWER+ shutdown the display screen indicates a load of zero amps, the UPS status is "OK,
OFF"; the Static Switch status is "OK, BYP".
L1:__________
L2:__________
L3:__________
1.
Press twice on the On/Off button on the upper right of the system controller panel.
Wait about 2 minutes for the POWER + to start up.
The following screen is displayed:
LOAD LEVEL
L1:__________
L2:__________
L3:__________
The UPS status should now be "OK, ON" and the STSW status "OK INV".
POWER +
UPS,
PARALLEL
USER GUIDE
G
AMATRONIC
OUTINE START
LOAD LEVEL
000A, 230V
000A, 230V
000A, 230V
Figure 60: Main screen after a power shutdown
Figure 61: Main screen after a power shutdown indication
000A, 230V
000A, 230V
000A, 230V
Figure 62: Main screen at power-up
,
. 2.0
REL
E
I
L
LECTRONIC
NDUSTRIES
TD
-
UP
---22:21:18---
BATTERY:
UPS OK
STSW OK
---22:21:18---
BATTERY:
UPS OK
STSW OK
(INV)
.
.
864V
(OFF)
(BYP)
864V
(ON)
Status
indications
After
51