Bypass Operation (Automatic); Bypass Operation (Manual); Figure 35: Ac Power Failure Indication; Figure 36: Ups In Bypass Mode - Gamatronic POWER+ User Manual

Parallel multi-system configuration
Hide thumbs Also See for POWER+:
Table of Contents

Advertisement

4.9.3

Bypass operation (automatic)

During Bypass operation, the ac feeds the load via the bypass static switch. The red alarm flashes to
indicate an abnormal status.
L1:
L2:
L3:
4.9.4

Bypass operation (manual)

If the Power+ is manually switched to bypass operation by pressing the Inv/Byp button, the load is
transferred to the mains ac input line. Transfer back to normal operation must be performed manually. The
red alarm indicator flashes to indicate an abnormal status (see Figure 37).
IMPORTANT OPERATIONAL NOTE:
When two (or more) Power+ units are being operated in parallel mode, and the system is manually moved
to bypass mode, the return of the system to Inverter mode must be performed on the same unit that was
used to transfer the system to bypass mode. If you attempt to return the system to Inverter mode on a unit
other than the one that was used to put the system in bypass mode, the command will not be accepted.
POWER +
UPS,
PARALLEL
USER GUIDE
G
AMATRONIC

Figure 35: Ac power failure indication

LOAD LEVEL
_____
015A, 230V
_____
012A, 230V
______
011A, 230V

Figure 36: UPS in bypass mode

Figure 37: UPS in bypass mode

,
. 2.0
REL
E
I
L
LECTRONIC
NDUSTRIES
TD
---12:01:11---
BATTERY:
UPS OK
STSW OK
.
868V
(ON)
Status
(BYP)
indications
-
39