7.4

"Self-test" Option

You can run a self-test at any time without interfering in the normal operation of the POWER + . A self-test is
also initiated by the POWER + itself each day at midnight.
The failure of a self-test sets on the self-test alarm. The self-test alarm can only be cleared by a subsequent
successful self-test, or it can be cleared manually by a maintenance technician. Powering the POWER +
down and up, for example, does not clear the self-test alarm. This is because the failure of a self-test is
considered a serious event that should not be "forgotten". A self-test failure is also recorded in the alarm
log.
[Main Menu > SELFTEST]
Wait for results...
STATIC RAM: PASSED
EEPROM – 1: PASSED
EEPROM – 3: PASSED
68
G
E
AMATRONIC
LECTRONIC

Figure 99: Main Menu option 3 ("Self Test")

R.T
DC SUPPLIES: PASSED

Figure 100: Result screen from self-test

I
L
.
NDUSTRIES
TD
CLOCK: PASSED
POWER +
PARALLEL
UPS,
,
. 2.0
USER GUIDE