4.10
Configuration
Perform the following configuration steps from the control panel for each UPS.
4.10.1
Check Configured Modules
Verify that the number of configured modules matches the desired output power, and verify that the number
of redundant modules is correct. Modify as needed.
1.
Press Ent to reach the Main Menu.
1> SYSTEM
2> UPS MODULE
3> SELFTEST
NAVIGATE: <UP, DOWN> 1 SELECT: <ENTER>
2.
From the Main Menu select option 7, Setup.
[Main Menu > SETUP]
Type in Level-1 PASSWORD, THEN – ENTER
Your privilege will expire after 15 min.
PASSWORD:________
3.
When the Password access panel appears, enter the password and press Ent. The factory default
password is to press the
Note: If the password has been changed and the system does not accept it, request from your system
administrator the technician password, which cannot be changed, and use it to reset the user
password.
4.
Select Service, option 8:
[Main Menu > SETUP > (password) > Ent]
1> Alarm set
2> Module conf. 6> Site
3> Battery
4> Charge
POWER +
UPS,
PARALLEL
USER GUIDE
G
E
AMATRONIC
LECTRONIC
4> HISTORY
5> BATTERY
6> ALARM
Figure 38: Main Menu
POWER+ System Setup
Figure 39: Password access
key 8 times.
5> Time
7> Password #1
8> Service
Figure 40: Setup menu
,
. 2.0
REL
I
L
.
NDUSTRIES
TD
7> SETUP
8> STATIC SW
9> _____
9> Silicon
41