Setting Disable Temperature Compensation; Setting Absolute Maximum And Minimum Voltages; Figure 177: Battery Setup Menu; Figure 178: Enable/Disable Temperature Compensation - Gamatronic POWER+ User Manual

Parallel multi-system configuration
Hide thumbs Also See for POWER+:
Table of Contents

Advertisement

7.10.6

Setting Disable Temperature Compensation

1.
Select Temp Compensat.:
[Main Menu > SETUP > (password) > Battery]
1> Test-Voltage
2> Test Alarm
3> Current-Limit.. 7> 'AuTo' Test
4> Temp Compensat. 8> Enable/Dis Options
2.
Select Enable Temp. Compensation and press Ent to toggle enable/disable:
[Main Menu > SETUP > (password) > Battery > Temp.Compensat.]
1> Temperature Compensation Value Setup
2> Enable Temp. Compensation
3> Set ABSOLUTE Max & Min Voltages
Press '2' to toggle enable / disable
1> Temperature Compensation Value Setup
2> Disable Temp. Compensation
3> Set ABSOLUTE Max & Min Voltages
Press '2' to toggle enable / disable
7.10.7

Setting Absolute Maximum and Minimum Voltages

1.
Select Set ABSOLUTE Max & Min Voltages:
[Main Menu > SETUP > (password) > Battery > Temp. Compensat.]
1> Temperature Compensation Value Setup
2> Enable Temp. Compensation
3> Set ABSOLUTE Max & Min Voltages
Press '2' to toggle enable / disable
POWER +
UPS,
PARALLEL
USER GUIDE
G
E
AMATRONIC
5> Battery test...
6> Capacity 0020 AH)

Figure 177: Battery setup menu

Figure 178: Enable/Disable temperature compensation

Figure 179: Select Set ABSOLUTE Max & Min Voltages
,
. 2.0
REL
I
L
.
LECTRONIC
NDUSTRIES
TD
(
(2.0 mV)
(
OFF)
1
1
OFF)
1
97