Battery; Table 1: Battery Lifetime Vs Environmental Temperature - Gamatronic POWER+ User Manual

Parallel multi-system configuration
Hide thumbs Also See for POWER+:
Table of Contents

Advertisement

1.4

Battery

The POWER + battery bank is used as a backup in the event that the utility ac input fails.
Batteries are charged by the rectifier which supplies both the inverter and the battery charger.
For systems from 10kVA through 40kVA, the batteries may be housed internally; however for systems
from 50kVA through 100kVA, or for sites where a long backup duration is required, the batteries are
housed in an external cabinet. The battery cabinet should be installed as close to the UPS as is practically
possible.
Protect the batteries from moisture, dampness, and foreign substances. The temperature of the battery's
environment influences the batteries' useful lifetime.
POWER +
UPS,
PARALLEL
USER GUIDE
G
E
AMATRONIC

Table 1: Battery lifetime vs environmental temperature

E
NVIRONMENTAL
TEMPERATURE
20 °C
30 °C
40 °C
,
. 2.0
REL
I
L
.
LECTRONIC
NDUSTRIES
TD
A
CHIEVABLE PERCENTAGE OF
'
BATTERY
S RATED LIFETIME
100 %
50 %
20 %
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents