Table 9: Log Messages - Gamatronic POWER+ User Manual

Parallel multi-system configuration
Hide thumbs Also See for POWER+:
Table of Contents

Advertisement

Message
#
01
UPSMAJ
02
UPSMIN
03
------
04
------
05
LOADBP
06
VIBRA_
07
OVTEMP
08
OUTFLT
09
BAT-HI
10
------
11
BATEND
12
BATLOW
13
STSWRN
14
E.P.O.
15
EQ-HST
16
BATFLT
17
USER-1
18
USER-2
19
USER-3
20
AC-BRN
21
ACIN_H
22
ACFAIL
23
STSWCM
24
SLFFLT
25
BAT-CB
26
CURSHR
27
UPSOUT
28
UPSHDN
29
OVLOAD
POWER +
UPS,
PARALLEL
USER GUIDE
G
AMATRONIC

Table 9: Log Messages

Explanation
More than 1 UPS Module is sending an alarm or fault warning
Single UPS Module is sending an alarm or fault warning
N.A.
N.A.
Load is now running on bypass. See Table 10 on page 72 to interpret the
LOADBP value.
Alarm(s) vibrating. Alarm is frequently raised and lowered. Ignore to avoid
loading the log filling up.
Excess temperature
No ac output to load
Excessive battery voltage
N.A.
End of battery backup. Battery is discharged to shutdown limit
Low battery voltage
Static Switch Warning or alarm
Emergency Power Off is active
Battery is currently charging in equalizing mode, dc voltage is temporarily
increased
Batteries failed last test
User 1 input open
User 2 input open
User 3 input open
Input ac supply Brown Out
Ac input excessive
Ac input failure
Static Switch does not respond
Last controller self-test failed
Battery Circuit Breaker Open
Current Sharing fault, load current is not equally divided between modules
Fault (no current) in 1 or more output stage
UPS shutdown by EPO, Battery Discharge, ON/OFF pressed
Load current is high
,
. 2.0
REL
E
I
L
LECTRONIC
NDUSTRIES
TD
.
71

Hide quick links:

Advertisement

Table of Contents
loading