Setting Frequency Limits; Calibrating Dc Voltage; Figure 152: Module Config. Setup Menu; Figure 153: Select The Frequency Limits - Gamatronic POWER+ User Manual

Parallel multi-system configuration
Hide thumbs Also See for POWER+:
Table of Contents

Advertisement

7.9.6

Setting Frequency Limits

1.
Select Frequency Limits:
[Main Menu > SETUP > (password) > Module conf.]
1. Num of phase
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage
4. Update Vo/Fr/ph
Using the ▲▼ keys set the frequency limits, press Ent, and then Esc:
2.
[Main Menu > SETUP > (password) > Module conf. > Frequency Limits]
---
1: No Change
2: +/- 1Hz
3: +/- 2Hz
7.9.7

Calibrating DC Voltage

1.
Select DC Calibration:
[Main Menu > SETUP > (password) > Module conf.]
1. Num of phase
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage
4. Update Vo/Fr/ph
2.
Select either Calibrate Positive Voltage or Calibrate Negative Voltage and then press Ent:
[Main Menu > SETUP > (password) > Module conf. > DC Calibration]
--- MODULES DC VOLTAGE CALIBRATION ---
SELECT – 1: Calibrate Positive Voltage
SELECT – 2: Calibrate Negative Voltage
Then press ENTER to continue
POWER +
UPS,
PARALLEL
USER GUIDE
G
E
AMATRONIC
5.Output Adjust
7.DC Calibration
8.AC Calibration

Figure 152: Module Config. setup menu

Set frequency limits
4: +/- 3Hz
(slctd) 5: +/- 4Hz
6: +/- 0.5Hz

Figure 153: Select the frequency limits

5.Output Adjust
7.DC Calibration
8.AC Calibration

Figure 154: Module Config. setup menu

Figure 155: Calibrate Positive or Negative Voltage

,
. 2.0
REL
I
L
.
LECTRONIC
NDUSTRIES
TD
---
89