Selecting Standalone Or Parallel Operation; Figure 238: Calibrating Dc Current; Figure 239: Entering Actual Current; Figure 240: Service > Configure Menu - Gamatronic POWER+ User Manual

Parallel multi-system configuration
Hide thumbs Also See for POWER+:
Table of Contents

Advertisement

5.
Press Ent to continue:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration > DC-I Calibration]
1> Calibrate Battery #1 Current
6.
Using the arrow keys, set the actual current and then press Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration > DC-I Calibration >
Ent]
CURRENT METER #01 CALIBRATION
Enter the value of the actual current:
7.12.3.7

Selecting Standalone or Parallel Operation

1.
Select Parallel/StandAlone:
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total)
3> # OF BATT
4> Static Switch Setup
Select Stand Alone or Parallel by using the ▲▼arrow keys and Ent:
2.
[Main Menu > SETUP > (password) > Ent > Service > Configure > Parallel/StandAlone]
---
Parallel / Stand-Alone Setup
SELECT - 1: Stand Alone
SELECT - 2: Parallel
116
G
E
AMATRONIC
LECTRONIC

Figure 238: Calibrating DC current

02000

Figure 239: Entering actual current

7> Parallel/StandAlone
Figure 240: Service > Configure menu

Figure 241: Setting standalone or parallel operation

I
L
.
NDUSTRIES
TD
(X0.1)A
6> Calibration
8> REM COMMAND
---
(selected)
POWER +
UPS,
,
PARALLEL
USER GUIDE
. 2.0
REL