7.12.3.8

Enabling/Disabling Remote Commands

1.
Select REM COMMAND:
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total)
3> # OF BATT
4> Static Switch Setup
Enable or disable remote commands by using the ▲▼arrow keys and Ent:
2.
[Main Menu > SETUP > (password) > Ent > Service > Configure > REM COMMAND]
---
REMOTE COMMANDS EN / DIS
SELECT - 1: Disable
SELECT - 2: Enable
7.12.4

Enabling/Disabling Current Sharing

1.
Select En/Dis shar:
[Main Menu > SETUP > (password) > Ent > Service]
1> ------
2> UPSs
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter
Enable or disable current sharing by using the ▲▼arrow keys and Ent::
2.
[Main Menu > SETUP > (password) > Ent > Service > Configure > En/Dis shar]
SELECT 1: RST CURRSHAR DISBLD:(selected)
SELECT 2: RST CURRSHAR ENBLD:
---
CURRENT SHARIN RESET EN / DIS
POWER +
UPS,
PARALLEL
USER GUIDE
G
E
AMATRONIC
LECTRONIC
7> Parallel/StandAlone
Figure 242: Service > Configure menu

Figure 243: Enabling/disabling remote commands

4> DryOut Test 7> --------
5> Configure

Figure 244: Service menu

Figure 245: Enabling/disabling current sharing

,
. 2.0
REL
I
L
.
NDUSTRIES
TD
6> Calibration
8> REM COMMAND
---
(selected)
8> Powr.Calib
---
117