3.
Use the arrow keys to set BATEND and press Ent:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT > BATEND]
FLOATING CHARGE ALARM SETUP
VOLTAGE SETTING: 340.0V
4.
Select BATLOW:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT]
1> BATEND
2> BATLOW
3> ------
4> BAT-HI
5.
Use the arrow keys to set BATLOW and press Ent:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT > BATLOW]
FLOATING CHARGE ALARM SETUP
VOLTAGE SETTING: 360.0V
6.
Select BAT-HI:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT]
1> BATEND
2> BATLOW
3> ------
4> BAT-HI