Figure 126: Set Batend; Figure 127: Battery Floating Charge Alarm Setup Menu; Figure 128: Set Batlow; Figure 129: Battery Floating Charge Alarm Setup Menu - Gamatronic POWER+ User Manual

Parallel multi-system configuration
Hide thumbs Also See for POWER+:
Table of Contents

Advertisement

3.
Use the arrow keys to set BATEND and press Ent:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT > BATEND]
FLOATING CHARGE ALARM SETUP
VOLTAGE SETTING: 340.0V
4.
Select BATLOW:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT]
1> BATEND
2> BATLOW
3> ------
4> BAT-HI
5.
Use the arrow keys to set BATLOW and press Ent:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT > BATLOW]
FLOATING CHARGE ALARM SETUP
VOLTAGE SETTING: 360.0V
6.
Select BAT-HI:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT]
1> BATEND
2> BATLOW
3> ------
4> BAT-HI
POWER +
UPS,
PARALLEL
USER GUIDE
G
E
AMATRONIC
LECTRONIC

Figure 126: Set BATEND

Figure 127: Battery floating charge alarm setup menu

Figure 128: Set BATLOW

Figure 129: Battery floating charge alarm setup menu

,
. 2.0
REL
I
L
.
NDUSTRIES
TD
SELECT ITEM:1
SELECT ITEM:1
81