3.
Adjust the measured value using the arrow keys, and press Ent to update:
[Main Menu > SETUP > (password) > Module conf. > DC Calibration > Ent]
MODULE V. CALIB –
#######
MEASURED VALUE:
7.9.8
Calibrating AC Voltage
1.
Select AC Calibration:
[Main Menu > SETUP > (password) > Module conf.]
1. Num of phase
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage
4. Update Vo/Fr/ph
2.
Select either Calibrate INPUT Voltage or Calibrate OUTPUT Voltage and then press Ent:
[Main Menu > SETUP > (password) > Module conf. > AC Calibration]
--- MODULES AC VOLTAGE CALIBRATION ---
SELECT – 1: Calibrate INPUT
SELECT – 2: Calibrate OUTPUT Voltage
Then press ENTER to continue
3.
Adjust the measured value using the arrow keys, and press Ent to update:
[Main Menu > SETUP > (password) > Module conf. > AC Calibration > Ent]
MODULE V. CALIB –
#######
MEASURED VALUE:
90
G
E
AMATRONIC
LECTRONIC
15 Sec to expire
Press ENTER To UPDATE
432.0V
Figure 156: Enter measured value
5.Output Adjust
7.DC Calibration
8.AC Calibration
Figure 157: Module Config. setup menu
Figure 158: Calibrate INPUT or OUTPUT Voltage
15 Sec to expire
Press ENTER To UPDATE
240.0V
Figure 159: Enter measured value