7.10.12 Activating 'Auto' Test
1.
Select 'AuTo' Test:
[Main Menu > SETUP > (password) > Battery]
1> Test-Voltage
2> Test Alarm
3> Current-Limit.. 7> 'AuTo' Test
4> Temp Compensat. 8> Enable/Dis Options
2.
The test is performed. Press Ent when done.
[Main Menu > SETUP > (password) > Battery > 'Auto' Test]
Max/estim time left : 00:00:00 /--:--:--
Battery test in progress for:
Batt. volt: 860.0V
Last test: PASSED
7.10.13 Enabling/Disabling Options
1.
Select Enable/Dis Options:
[Main Menu > SETUP > (password) > Battery]
1> Test-Voltage
2> Test Alarm
3> Current-Limit.. 7> 'AuTo' Test
4> Temp Compensat. 8> Enable/Dis Options
2.
Select ENABLE SHUTDOWN by long AC FAIL (Off) and press Ent to toggle enable/disable:
[Main Menu > SETUP > (password) > Battery > Enable/Dis Options]
1> ENABLE SHUTDOWN by long AC FAIL (Off)
2> ENABLE Current Sensors
3> ENABLE BATT Temperature sensor
Select & Press To toggle Enable/Disable
1> DISABLE SHUTDOWN by long AC FAIL(On )
2> ENABLE Current Sensors
3> ENABLE BATT Temperature sensor
Select & Press To toggle Enable/Disable
102
G
E
AMATRONIC
5> Battery test...
6> Capacity 0020 AH)
Figure 196: Battery setup menu
Batt.current: 008
Figure 197: Activated 'Auto' test
5> Battery test...
6> Capacity 0020 AH)
Figure 198: Battery setup menu
Figure 199: Enable/Disable shutdown by long AC failure