Power + Control Screen; Load-Level Bar Graph; Figure 28: Power+ Control Screen - Gamatronic POWER+ User Manual

Parallel multi-system configuration
Hide thumbs Also See for POWER+:
Table of Contents

Advertisement

POWER + control screen

4.4
The POWER + control screen is illustrated below. It is part of the control panel described on page 32.
How to read and understand the POWER + control screen is described in detail in Chapter 6, POWER +
control panel, beginning on page 55.
The control screen provides menus and displays all aspects of the POWER + systems input, output and
static switch as well as operational details. The figure below shows the POWER + 3-phase display.
L1:
L2:
L3:
This is how the control screen appears while the UPS is running normally.
4.4.1

Load-level bar graph

The load-level bar graph on the default screen display illustrates the approximate load on each output
phase of the UPS, as a percent of the maximum available output for each phase.
The load on each phase is represented by a series of from 1 to 10 dots. Each dot represents about 10 % of
the maximum available output per phase.
The dots can be either filled in (black) or clear (white). The number of black dots represents kW, and the
number of black and white dots together represents kVA (apparent power).
For example, in Figure 28, the load on Line 2 is 30 % (3 black dots) of the maximum in terms of kW, and
40 % (3 black dots plus 1 white dot) of the maximum in terms of kVA.
To compute the approximate value in kW or kVA of each dot:
1.
Compute the maximum load per phase =
10 kVA [or 8 kW]
3 phases
2.
Dividing the maximum load per phase by 10 gives you the value of 1 dot.
Example: Assume a system with 10 modules, 2 of which are redundant.
10 kVA / 3 x (10-2) = 3.33 x 8 = maximum load per phase = 26.67 kVA.
Thus, 26.67 / 10 = 2.67 kVA is the approximate value of each dot.
34
G
AMATRONIC
Load level
Output
bar graph
current
LOAD LEVEL
_____
015A, 230V
______
012A, 230V
_______
011A, 230V

Figure 28: POWER+ control screen

x (total # of modules - redundant # of modules)
E
I
L
LECTRONIC
NDUSTRIES
TD
Output
Current
voltage
---11:20:25---
BATTERY:
UPS OK
STSW OK
POWER +
.
time
Battery
864V
voltage
(ON)
Status
(INV)
indications
UPS,
PARALLEL
USER GUIDE
,