7.15.8
Setting the Menu Language
Select the desired menu language using the ▲▼ keys and press Ent:
[3-second Esc > Language]
-----
SELECT - 1: English
SELECT - 2: Spanish
SELECT - 3: Portuguese
7.15.9
System Parameter Settings
User the arrow keys ▲▼ to select General, and then press Ent:
[3-second Esc]
1> UPSs Stat
2> UPSs On/Off
3> SoftWare Rev
4> Network...
7.15.9.1
First General Screen
A description of the various system parameters shown in screen 1 are listed below.
[3-second Esc > GENERAL]
ACV:220...ALM:242/185
MODULES:07/02
DCV:432...ALM:475/360/340
BATT...TEST:04/05/360/352...CAP: 0010 AH
a.
ACV: nominal value of the input/output ac voltage (220 for 2x32 batteries; 110 for 2x16 batteries).
b.
ALM: input ac voltage alarm HIGH/LOW.
c.
TEMP. ALARM: high temperature limit for an external temperature sensor.
d.
MODULES: QUANTITY/REDUNDANCY: 07/02 in the screen means that 7 modules are
presented in the system, 2 modules are reserve (full load is 10 kVA*(7-2)=50 kVA / 40 kW).
e.
C.LIM.=off (VALUE): battery current limit function is de-activated (off) or maximum battery current
value in Amps. If C.LIM is activated, the system must be equipped with an optional battery current
sensor.
f.
T.C. = 2.0mV: negative temperature coefficient of the battery dc voltage in mV per °C per battery
cell. Nominal temperature is 25 °C. For dc nominal voltage 432 V , temperature 35 °C, 32
128
G
E
I
AMATRONIC
LECTRONIC
NDUSTRIES
LANGUAGE SETUP
Figure 281: Set menu language
5> Dry In/Out Stat
6> Alarms Status
7> Language
1
8> General
Figure 282: Select General
C.LIM= off , T.C= 2.0mV
Figure 283: General (Screen 1)
L
.
TD
-----
(selected)
TEMP. ALARM:45C
POWER +
PARALLEL
UPS,
,
. 2.0
USER GUIDE
REL