15. POWER +
TECHNICAL DATA FOR A SINGLE POWER
Topology
Construction
Operation
Input
Voltage
Voltage range
Current
Frequency
Power walk-in
Power Factor
THDI
Output
Rated Power
Frequency tracking range
Slew rate
Voltage
Static Regulation
Regulation for unbalanced load
Dynamic response to 100% load step
Overload
Waveform
THD
Load CF
AC-AC efficiency (nominal)
DC-AC efficiency (nominal)
Batteries
DC-Link Voltage
Quantity
Type
General
Max. power dissipation (Po=80 kW)
Ambient temperature Operating:
Relative humidity
Altitude
Enclosure
Cooling system
Standards
EMC
Design
Safety
Low magnetic field radiation
Dimensions
UPS type
Height (cm)
Width (cm)
Depth (cm)
Weight
Acoustic Noise
Noise (dBA) with half load
Noise (dBA) with full load
All specifications are subject to change without notice.
Operation of the UPS in a parallel configuration may slightly alter the performance characteristics.
158
G
E
AMATRONIC
SPECIFICATIONS

Table 20: Specifications

Storage:
10
20
30
kVA
kVA
kVA
71
80
119
134
149
48
52
51
54
I
L
.
LECTRONIC
NDUSTRIES
TD
+
SYSTEM (PARALLEL MODEL)
On line battery, double conversion, VFI
Modular parallel hot-plugged modules
Continuous
3 × 400 Vac + N (3 x 230 Vac + Neutral)
– 27 % and + 20 %
3 × 15 A per module – no inrush current at startup
47-63 Hz
> 60 sec.
0.99
5 %
10 kVA / 8 kW per module
±2 Hz
1 Hz/sec
3 × 400 Vac + N (3 x 230 Vac + Neutral)
±1 %
±1 for 100% unbalanced load
±2 %
110% for 10 min., 125% for 60 sec., 1000% for 1 cycle
Sinusoidal
Less than 2 % for linear load
6:1
Up to 96 % at full load
Up to 98 % at full load
±340 to ±425 Vdc
64 × 12 Vdc
Sealed, lead acid, rechargeable
2664 W (9088 BTU) for 8 modules
-10 to +40 °C (14 to 104 °F)
-20 to +60 °C (-4 to 140 °F)
95 % max., non-condensing
1500 m without derating
IP20
Multi-Fan with speed control (forced)
IEC 62040-2, under EMC 2004/108/EC
IEC 62040-3
IEC 62040-1, under LVD 2006/95/EC
EMF as per ICNIRP
40
50
kVA
kVA
90
99
108
60
95
164
179
53
54
55
55
57
58
POWER +
60
70
80
kVA
kVA
kVA
118
127
136
204
219
234
55.8
56.4
57
58.8
59.4
60
UPS,
PARALLEL
USER GUIDE
90
100
kVA
kVA
146
155
249
264
57.5
58
60.5
61
,
. 2.0