11. Select Store:
[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network]
1> Set IP ADDRESS
2> Set GATEWAY
3> Set MASK
4> Store
Entered information is stored.
12. Select SNMP factor:
[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network]
1> Set IP ADDRESS
2> Set GATEWAY
3> Set MASK
4> Store
13. Use the arrows keys to set the SNMP NO COMM Factor, press Ent and then Esc:
[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network > SNMP factor]
Set SNMP NO COMM Factor Value
14. Select Reset MBX:
[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Reset MBX]
1> Restart controller 3> Network...
2> Factory settings
Your selection: 1
Enter if you are sure (else press Esc.!)
The MBX is reset.
POWER +
UPS,
PARALLEL
USER GUIDE
G
E
AMATRONIC
LECTRONIC
157.211.000.253
157.211.000.251
255.255.255.000
5> SNMP factor
Figure 258: Network menu
157.211.000.253
157.211.000.251
255.255.255.000
5> SNMP factor
Figure 259: Network menu
(10 - 99)
50
Figure 260 : Setting the SNMP NO COMM factor
4> Reset MBX
5> --------------
Figure 261: SC2012 menu
,