Calibrating DC Currents

1.
Select Calibration:
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total)
3> # OF BATT
4> Static Switch Setup
2.
Select DC-I Offset removal:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration]
1> -----
2> DC-I Offset removal 6> -----
3> DC-I Calibration
4> -----
3.
Follow screen instructions:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration > DC-I Offset
removal]
To remove current offsets,
DISCONNECT BATTERIES and LOAD first,
Then, press ENTER.
Else, press Esc.
4.
Select DC-I Calibration:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration]
1> -----
2> DC-I Offset removal 6> -----
3> DC-I Calibration
4> -----