Section 5 • Fault Codes
Load Sense System Fault Codes
Error Source 12, System Checks
Error Type
ID Name
11 Safety envelope reached
12 Platform load greater
than 1250 lbs/567 kg
13 CAN communication failure
14 Sensor power failure
21 Angle sensor
not active
22 String potentiometer
not active
23 Power relay output
short high
24 Power relay output
short low
25 Directional relay output
short high
26 Output short low
5 - 22
Condition
Power relays disengaged.
Power relays disengaged.
Power relays disengaged.
Power relays disengaged.
Power relays disengaged.
Power relays disengaged.
Power relays disengaged.
Relay wiring open or
shorted to voltage.
Power relays disengaged.
Relay wiring open or
shorted to ground.
Boom up/down and
extend/retract inoperative.
Relay wiring open or
shorted to voltage.
Boom up/down and
extend/retract inoperative.
Relay wiring open or
shorted to ground.
S-60 • S-65 • S-60 TRAX • S-65 TRAX
S-60 HC • S-60X • S-60XC
Solution
Use recovery switch and APU from the
ground controls to recover the
machine to stowed position or within the
operating envelope.
Remove weight from platform until load is
1200 lbs/544 kg or less.
Repair CAN bus wiring and/or
connections.
Use recovery switch and APU from the
ground controls to recover the machine
to stowed position or within the operating
envelope.
Inspect boom angle sensor for
proper operation and be sure it is
connected to boom properly OR replace
boom angle sensor.
Inspect string potentiometer for proper
operation and be sure it is connected to
boom properly OR replace string
potentiometer.
Repair system wiring and/or connections.
Repair system wiring and/or connections.
Repair system wiring and/or connections.
Repair system wiring and/or connections.
December 2013
Part No. 147753