Initialize Counting Direction; Initializing Home Position - BONFIGLIOLI Active Cube User Manual

Frequency inverter 230 v/400 v
Hide thumbs Also See for Active Cube:
Table of Contents

Advertisement

6.6.2 Initialize counting direction

First check if the counting direction of the user units meets the requirements. You can
change the counting direction by inverting the parameter
513 (e.g. by inverting parameter
tor
to -200.00).
Danger!

6.6.3 Initializing home position

For positioning application, a certain point of the system is typically defined as the
home position. After checking the correct reference system of the positioning and
linear encoder (see Chapter 6.6.1) and setting the counting direction, the home posi-
tion can be initialized.
Move (e.g. in JOG mode) to the required system home position. At this position, stop
the drive. Set parameter
Note:
Now, read the value in parameter
inverted value in
Example:
Act. Position
Once you have set up the home position offset, check the system for correct function
again (see chapter 6.6.1).
If required for the application, set up the software limit switches now.
Note:
03/12
By changing parameter
values will be re-calculated in the internal user unit format. As a result,
the value of
Act. Position
limit switches are used or in the case of feedback to a PLC, this can result
in warnings or application errors. For this reasons, after changing the
parameters of the reference system and the encoder, always check the
1108, considering the permissible travel distance (e.g.
Act. Position
1145).
SW Limit Switch
Home Offset
By default,
Home Offset
you do not have to change the value, but this step is required in the case
of commissioning following a change.
1131.
Home Offset
1108 = 7654 u
Referencing using an absolute value encoder is not necessary after com-
pletion of first commissioning. The referencing setting
1220 with setting "10 – No referencing required" can be used after
mode
initialization.
EM-ABS-01 for ACU
EC2 Gear Factor Numerator
EC2 Gear Factor Numerator
1108 may change. Especially when software
1131 = 0.
1131 is set to zero. Upon first commissioning,
1108. Invert this value. Enter the
Act. Position
1131 = - 7654
Home Offset
EC2 Gear Factor Numera-
513 from 200.00
513, the encoder
Pos.
Operation
43