8.1.3 Operation modes

The operation modes of the analog input characteristic enable application-related scal-
ing as a supplement to the characteristic points mentioned above. One of the four
linear types of characteristic is selected for the signal adaptation for the analog input
signal via parameter
characteristic selected, they are corrected internally.
Operation mode
1 - bipolar
11 - unipolar
21 - unipolar 2-10V/4-20mA
101 - bipolar abs.
Further information on the operation modes stated in the table can be found in the
following chapter "Examples".
8.1.3.1

Examples

The analog input signal is mapped onto a reference value as a function of the charac-
teristic selected. The following examples show the operation modes for an analog
voltage signal. The parameter
0.00 Hz. The characteristic point 100% for the Y axis corresponds to the parameter
Maximum Frequency
Attention! The various operation modes change the input characteristic as a
In operation mode "1 – bipolar", the characteristic of the analog input can be freely
set by stating two characteristic points.
(X1=-70% / Y1=-50%)
03/12
Operation mode
562
Minimum Frequency
419 of 50.00 Hz in the examples.
func-tion of the characteristic points parameterized. In the following ex-
amples, the areas of the system of coordinates from which a characteristic
point is displaced are marked.
Operation mode "1 – bipolar"
Y
(X2=80% / Y2=85%)
42.50Hz
-7V
-25Hz
EM-ABS-01 for ACU
562. If the points are not suited for the type of
Function
The analog input signal is mapped onto the reference
value according to the points (X1/Y1) and (X2/Y2).
With a negative parameter value of the points X1 or
X2, the latter are mapped to the reference value ze-
ro.
If the points X1 or X2 have been set with a negative
parameter value or less than 0%, the input characte-
ristic is mapped to the reference value 20%.
Negative parameter values of the points Y1 or Y2 are
mapped as a positive reference value in the characte-
ristic.
418 has been set to the value
Point 1:
X1 = -70.00% · 10 V = -7.00 V
Y1 = -50.00% · 50.00 Hz = -25.00 Hz
Point 2:
X2 = 80.00% · 10 V = 8.00 V
Y2 = 85.00% · 50.00 Hz = 42.50 Hz
X
Tolerance band:
8V
ΔX = 2.00% · 10 V = 0.20 V
The direction of rotation is changed in this
example at an analog input signal of 
 - 1.44
V, with a tolerance band of ±0.20 V.
85