Management Module Switchover

Events that Cause a Switchover

There are a number of events that can cause the active management module
to switchover to the standby management module when redundancy is
enabled:
The standby management module has not received a heartbeat for some
time from the active management module
The redundancy switchover command is executed
The active management module is hotswapped out
The MM Reset button on the active management module is pressed
The MM Shutdown button on the active management module is pressed
The boot or boot active command is executed
The reload command is executed
There is a hardware failure on the active management module
The active management module crashes
In all of these cases the standby management module takes control and
performs the actual switchover. The reason for the switchover is entered in
log messages on the newly active management module and to any configured
Syslog servers.
You should be at the global configuration level when executing these
commands, that is, Procurve(config)# as shown in the examples.

When Switchover Will not Occur

There are some events for which a switchover is not triggered:
When a boot system command is executed
When the Reset button on the System Support module is pressed
When redundancy is disabled, unless there is a hardware failure and the
system is rebooted.
Redundancy (Switch 8212zl)
Management Module Switchover
15-13