6-3-6. Regarding Trigger Setting

TRIGGER channel settings in the record program determine which type of input trigger will
initiate alarm record operation. To access TRIGGER sub menu, move cursor to TRIGGER
setting in RECORD menu and press ENTER. TRIGGER sub menu similar to below should
be displayed. Note that this menu is invalid for continuous record mode if ALARM REC
MODE is set to OFF or SEQUENCE.
TRIGGER settings have no effect on alarm display. If
TRIGGER is set to OFF, alarm channels will still be
displayed according to setting made in ALARM / LOSS /
SENSOR menu (see sec. '6-9. Alarms').
‡@
:
Where
Sets input trigger used for each channel. (Same type input does not have to be applied to all
channels.)
OFF
ALARM
SENSOR
ALM / SENS
Note
[TRIGGER]
CH1
•\ ALARM
CH3
•\ ALARM
CH5
•\ SENSOR
CH7
•\ SENSOR
CH9
•\ ALM/SENS
CH11 •\ ALM/SENS
CH13 •\ OFF
CH15 •\ OFF
SET
Alarm record operation not initiated.
Alarm record operation initiated via external sensor device input.
Alarm record operation initiated via sensor board installed to
CDR-16T.
Alarm record operation initiated via external sensor device input
and sensor board installed to CDR-16T.
62
CH2
•\ ALARM
CH4
•\ ALARM
CH6
•\ SENSOR
CH8
•\ SENSOR
CH10 •\ ALM/SENS
CH12 •\ ALM/SENS
CH14 •\ OFF
CH16 •\ OFF
EXIT