Check The Number Of Wall Outlets - Fujitsu Eternus2000 Manual

Disk storage system
Hide thumbs Also See for Eternus2000:
Table of Contents

Advertisement

3.1 Preparation
3.1.2

Check the number of wall outlets

Check the required type and number of the wall outlets.
Type of wall outlet connectors
All ETERNUS2000 device types include US spec. AC200-240V cables (with plug) as standard.
In addition, power cords must comply with the particular safety standards of the country of use. In some
cases, a power cord will need to be purchased locally to satisfy the relevant power safety requirements.
Table 3.1
Controller Enclosure
Drive Enclosure
AC200V outlet box
(1U)
AC200V outlet box
(4U)
Required Number of Power Outlets
ETERNUS2000 model 100
Table 3.2
Controller Enclosure
Drive Enclosure
AC Outlet Box
No. of power outlets
46
When determining the rack-mounting layout, consider the interaction
Point
between the position of each drive enclosure and AC outlet box in the rack
and the length of each cable.
For example, for something installed at the top of a 1,800mm rack, about
2m of cable will be required to reach the bottom of the rack.
Wall outlets and cable lengths
Cable type
ETERNUS2000
connector
IEC320 C13
Direct connection
Required number of Power Outlets (ETERNUS2000 model 100)
Component
Power outlet con-
nector
NEMA L6-15P
NEMA L6-20P
Combination pattern
1
1
1
0 − 1
0
1
0
0
1
2
4
2
ETERNUS2000 disk storage system User Guide
Copyright 2009 FUJITSU LIMITED
Cable
Note
length
4m
Max. rating: 250V 15A
(Normal usage <12A)
4m
Max. rating: 250V 20A
(Normal usage <16A)
P3AM-2512-03EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

100200