Required Number Of Outlets/Sockets; Circuit Protectors; Table 31 Required Conditions For Distribution Board Circuit Protectors - Fujitsu ETERNUS AB Series Site Planning Manual

Hide thumbs Also See for ETERNUS AB Series:
Table of Contents

Advertisement

1.
ETERNUS AB/HB Installation
Outlet/Socket Specifications

Required Number of Outlets/Sockets

The number of power outlets/sockets required to install the ETERNUS AB/HB depends on the num-
ber of shelves and power distribution units.
It is recommended that the power cords of the shelves are connected to the power distribution
units that are installed in the same rack. Secure the necessary number of power outlets within the
same rack to avoid connecting power cords to power outlets in different racks. It may be necessary
to purchase additional power distribution units depending on the installation locations of shelves.
Without Power Distribution Units
Two power sockets are required for each controller shelf and drive shelf.
With Power Distribution Units
Two power sockets are required for each power distribution unit.

Circuit Protectors

Protection coordination must be secured between the distribution board circuit protectors and the
ETERNUS AB/HB or power distribution units to protect the ETERNUS AB/HB by blocking the failed
circuit immediately when a power supply input error occurs.
Distribution board circuit protectors must satisfy the following required conditions and breaking
characteristics.
Required Conditions
The distribution board circuit protectors must satisfy the required conditions that are listed below.
Table 31
Required Conditions for Distribution Board Circuit Protectors
Power distribution unit (AC24A/200V, 2U, 16 outlets)
Power distribution unit (AC24A/200V, 2U, six outlets)
ETERNUS AB/HB (without power distribution units)
Connected device
Power supply voltage
AC 200 – 240V
AC 200 – 240V
AC 100 – 120V
AC 200 – 240V
44
Current capacity
24A
24A
15A
Site Planning Guide

Hide quick links: