Chapter 1
ETERNUS DX Installation
1.7
Outlet/Socket Specifications
1.7.2

Required Number of Outlets/Sockets

The number of power outlets/sockets required to install the ETERNUS DX depends on the number of drive
enclosures and power distribution units.
It is recommended that the power cords of the drive enclosures are connected to the power distribution units
that are installed in the same rack. Secure the necessary number of power outlets within the same rack to
avoid connecting power cords to power outlets in different racks. It may be necessary to purchase additional
power distribution units depending on the installation locations of enclosures.
Without Power Distribution Units
Two power sockets are required for each enclosure.
With Power Distribution Units
Two power sockets are required for each power distribution unit.
1.7.3

Circuit Protectors

Protection coordination must be secured between the distribution board circuit protectors and the ETERNUS
DX or power distribution units to protect the ETERNUS DX by blocking the failed circuit immediately when a
power supply input error occurs.
Distribution board circuit protectors must satisfy the following required conditions and breaking characteris-
tics.
Required Conditions
The distribution board circuit protectors must satisfy the required conditions that are listed below.

Table 1.11 Required Conditions for Distribution Board Circuit Protectors

Connected device
Power distribution unit (AC200-240V, 1U, 4 outlets)
Power distribution unit (AC200-240V, 2U, 12 outlets) AC 200 – 240V
Power distribution unit (AC200-240V, 2U, 16 outlets) AC 200 – 240V
ETERNUS DX (without power distribution units)
FUJITSU Storage ETERNUS DX60 S3 Disk storage system Site Planning Guide
Copyright 2015 FUJITSU LIMITED
Current capacity
Regions other than
the EMEIA, North
Power supply voltage
American, Central
American, and Car-
ibbean regions
AC 200 – 240V
15A
20A
30A
AC 100 – 120V
15A
AC 200 – 240V
25
The EMEIA, North
American, Central
American, and Car-
ibbean regions
16A
P3AM-8982-03ENZ0