10 | Specifications
10.2.2.1 Parameters for P(f)
Country-
Men
Display/
spec. Set-
u
Setting
tings
level
P(f) operation mode
Off | Mode 1 |
Mode 2
Power reference mode
with overfrequency
Actual power |
Nominal power
Power reference mode
with underfrequency
Actual power |
Nominal power
Dynamic gradient
1
2
3
4
4
mode
On | Off
Gradient with under-
frequency – feed-in
0 – 200 (%/Hz) /
40 (%/Hz) /
Gradient with overfre-
quency – feed-in
0 – 200 (%/Hz) /
40 (%/Hz) /
Gradient with overfre-
quency – charging
0 – 200 (%/ P
Hz) ;
40 (% P
1 [Hz]
Gradient with under-
frequency – charging
0 – 200 (%/Hz) ;
40 (% P
ref
[Hz]
Gradient
0 – 200 (%/Hz)
(%/Hz)
Maximum dynamic
gradient frequency
50.22 – 70.5 [Hz]
0.01 [Hz]
Minimum dynamic
gradient frequency
45 – 50 [Hz]
[Hz]
Page 74
Action in this menu/meaning
Activate or deactivate function.
Mode 1: With hysteresis activated.
Mode 2: Without hysteresis activated.
Power reference with overfrequency:
Power reference for power adjustment as in equation 2 and equation 3
for overfrequency incidents.
Power reference with underfrequency:
Power reference for power adjustment as in equation 2 and equation 3
for overfrequency incidents.
F Activate dynamic gradient.
NOTE: Gradient "Feed-in/charging with over/under frequency" is not
displayed.
Gradient with underfrequency (feed-in):
Determines the active power adjustment in accordance with equation 2
and equation 3, subject to the frequency.
1
Gradient for underfrequency incidents if the incident begins in feed-in
mode.
Gradient with overfrequency (feed-in):
1
Determines the active power adjustment in accordance with equation 2
and equation 3, subject to the frequency.
Gradient for overfrequency incidents if the incident begins in feed-in
mode.
Gradient with overfrequency (charging):
Determines the active power adjustment in accordance with equation 2
/
and equation 3, subject to the frequency.
ref
/Hz) /
Gradient for overfrequency incidents if the incident begins in charging
ref
mode.
Gradient with underfrequency (charging):
Determines the active power adjustment in accordance with equation 2
and equation 3, subject to the frequency.
/Hz) /
1
Gradient for underfrequency incidents if the incident begins in charging
mode.
Sets the active power change depending on the frequency according to
[See figure 58 [} Page 73] and [See figure 59 [} Page 73]
66
Dynamic gradient maximum frequency:
If dynamic gradient mode is activated, the gradient is calculated in order
to guarantee a linear power adjustment and reach the maximum char-
ging power if the frequency rises to the maximum configured frequency.
Dynamic gradient minimum frequency:
If dynamic gradient mode is activated, the gradient is calculated in order
0.01
to guarantee a linear power adjustment and reach the maximum feed-in
power if the frequency drops to the minimum configured frequency.