Sealing The Connection Area - Kaco blueplanet gridsave 92.0 TL3-S Manual

Hide thumbs Also See for blueplanet gridsave 92.0 TL3-S:
Table of Contents

Advertisement

Manual
Connect Powador-protect
(only for 380/400 V blueplanet 87.0TL3 / 92.0TL3 / 105TL3 / 100 NX3 / 125 NX3 )
↻ The cable to the external grid protection device is available on the device.
↻ Cover of the device has been opened.
1. Undo the cable fittings [ W_20]
2. Pass the connection cable through the cable fittings.
3. Connect wire A (+) to the terminal marked "INV OFF+" on the first device via the
"DO1" terminal of the protective device.
4. Connect wire B (-) to the terminal marked "INV OFF-" on the first device via the
"GND" terminal of the protective device.
5. Connect the other devices to one another as follows:
- wire A (+) to wire A (+) and wire B (-) to wire B (-).
6. Tighten cable fitting [ W_20 /
7. After commissioning: Configure the external Overvoltage protection
Powador-protect in the menu entry Features / Functions.
Connecting the external device
NOTE: When an external device is used, a separate power supply is also required
for this purpose. Some external devices only have a normally closed contact and
do not supply any voltage.
↻ The cable to the external grid protection device is available on the device.
↻ An external power supply is available at the grid protection device.
↻ Cover of the device has been opened.
1. Undo the cable fittings [ W_20]
2. Pass the connection cable through the cable fittings.
3. Connect the corresponding output of the external N/A protection to
"INV_OFF+", follow the operating instructions for the external device.
4. Connect the corresponding output of the external N/A protection to
"INV_OFF"-, -", follow the operating instructions for the external device.
5. Connect the other devices to one another as follows:
- wire A (+) to wire A (+) and wire B (-) to wire B (-).
6. After commissioning: Configure the external device Overvoltage protection in
the menu entry Features / Functions.
7.9

Sealing the connection area

↻ Grid connection is prepared.
1. Lift the housing cover onto the housing and loosely tighten the fastening screws.
2. Secure the housing cover (1) by tightening all 6 screws (2) in a diagonally oppos-
ite sequence [ T_25/ 5 Nm].
ð The device has been mounted and installed.
ð Put the device into operation.
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137
TL3-S
1,5 Nm ]
Installation | 7
x
RS485
A
B
A
B
GND
GND
2
1
A
x
y
RS485
A
B
A
B
GND
GND
Fig. 29: Connecting the device to
Powador-protect
x
RS485
INV
OFF
A
B
A
B
+
GND
GND
2
1
x
A
y
INV
RS485
OFF
A
B
A
B
+
GND
GND
Fig. 30: Connecting the device to
the external grid protection device
2
Fig. 31: Close the housing cover
Powador-
INV
protect
OFF
A
D01
GND
+
-
B
4
3
2
1
B
y
INV
OFF
INV Signal
+
-
External
device
A
14 NO
11 COM
12 NC
B
-
24
21
22
y
B
min./ max.
10-24V(+/-20%)
/15mA-1A
INV OFF
-
INV ON
Activ-Low signal
is required for
switching off
1