Kaco blueplanet gridsave 92.0 TL3-S Manual page 55

Hide thumbs Also See for blueplanet gridsave 92.0 TL3-S:
Table of Contents

Advertisement

Manual
Country-
Level Display/
spec. Set-
Setting
tings
Operation mode –
1
2
3
4
4
On | Off
Setting | Manual |Pre-
defined zero current
Priority – Reactive cur-
rent limitation | Active
current priority
Constant k positive se-
1
2
3
4
4
quence dip &
Constant k positive se-
quence swell
k 0 – 10
Constant k negative se-
4
1
2
3
4
quence dip
Constant k negative se-
quence swell
k 0 – 10
Dead band
1
2
3
4
4
2 – 120 [% Uref]
10.0
0.1
Dynamic reactive cur-
1
2
3
4
4
rent only
Off | On
Dead band mode
1
2
3
4
4
Mode 1 | Mode 2
Reference voltage
1
2
3
4
4
80.0 – 110.0 [%
Unom]
Minimum operating
1
2
3
4
4
voltage deactivation
45.0 – 125.0 [%
Unom]
Maximum operating
voltage deactivation
45.0 – 125.0 [%
Unom]
Password protection
Status
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137
TL3-S
Action in this menu/meaning
F Select a control process.
On: Activates dynamic grid support using dynamic reactive current.
Off: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to inter-
ference.
F Select a control process.
F Select a control process.
F Set amplification factor k for the pos. sequence for drop and increase
in the grid voltage.
2
0.1
F Set amplification factor k for the neg. sequence for drop and increase
in the grid voltage.
2
0.1
F Set dead band in %.
NOTE: With activated FRT mode, the pre-fault reactive current can be
added.
F If necessary, activate pre-fault reactive current.
F Select dead band mode for the active control process.
F Set reference voltage for the active control process.
100
0.1
F Set voltage range for the active control process.
0.1 &
0.1
Configuration and operation | 9
Page 55