Manual
Country-
Level Display/
spec. Set-
Setting
tings
Active power regula-
2
1
3
4
4
tion
Internal
3
4
1
2
4
Power Limitation
1
2
3
4
4
Status
Maximum apparent
1
2
3
4
4
power Slim
1000 –125000 /
[See sec-
tion 4} Page 12] [VA] /
100 [VA]
Maximum active power
1
2
3
4
4
Plim
1.0 – 100.0 [%
Slim] /
0.1
Password protection
Status
External
3
1
2
4
4
Power Limitation
1
2
3
4
4
Status
AC fallback active
1
2
3
4
4
power
0 – 100 [%Plim] /
100 [%Plim] /
Fallback time
1
2
3
4
4
0 – 43200 [s] /
300 [s] /
Output gradient limita-
1
2
3
4
4
tion increase & Output
gradient limitation de-
crease
1 – 65534 [% Slim /
min] /
Slim / min] /
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137
TL3-S
Action in this menu/meaning
NOTE: The output power of the device can be set permanently to a
lower value than the maximum output power via the active power
regulation.
NOTE: Option for internal power limitation as required by the grid op-
erator to limit the maximum power rating of the system at the grid
connection point. More detailed information at: [See sec-
tion 10.4.1} Page 79]
F Specify the activation status.
NOTE: The max. apparent power limits the internal power of the
device.
F Enter the value or set the value using the slider.
NOTE: The max. active power limits the internal power of the device.
F Enter the value or set the value using the slider.
100[% Slim] /
NOTE: The output power of the device can be set permanently to a
lower value than the maximum output power by the external power
limitation.
F Specify the activation status.
F Set fallback power.
Specifies the standard power in the event of a communication timeout.
If no active power command is received within the configured fallback
1
time, the device sets the power to the configured fallback power.
F Set the fallback time for the external power specification.
WARNING! After the set fallback time, external (RS485 or Modbus)
1
specifications for cos-phi, Q and P are reset to the relevant set fallback
value (cos-phi constant, Q-constant or fallback power).
NOTE: If the fallback time is set to 0s, external specifications for cos-
phi, Q and P are not reset (continued operation using the most re-
cently received target value).
1. Maximum change in the active power in the event of a change to
overexcited mode.
2. Maximum change in the active power in the event of a change to
underexcited mode.
65534 [%
1
Configuration and operation | 9