Active Power Regulation - Kaco blueplanet gridsave 92.0 TL3-S Manual

Hide thumbs Also See for blueplanet gridsave 92.0 TL3-S:
Table of Contents

Advertisement

10 | Specifications
Country-
Men
Display/
spec. Set-
u
Setting
tings
level
Output gradient in-
crease & Output gradi-
ent decrease
increasing | decreas-
ing
1 – 65,534 [% S
min] /
min] /
Settling time
1000 – 120000
[ms] /
10
Min. cos-phi Q1 - Min.
cos-phi Q4
0 – 1 /
0,001
Q1
Q4
Q2
Q3
Priority mode
Q-priority | P-prior-
ity
Active curve
1 – 4 / curve 1 TMP /
curve 2 / curve 3 /
curve 4
Number of nodes
2 – 10
1. node ... 10. node
Power | Voltage |
Excitation
0 – 100 [% S
43.6 [% S
Power | Voltage |
Excitation
0 – 125 [% S
43.6 [% U
Overexcited | under-
excited
10.2

Active power regulation

Dynamics / accuracy
In all of the control methods described below the specified target value at the inverter's connection terminals is adjusted
using a stationary deviation of the reactive power of maximum 2% S
Page 70
Action in this menu/meaning
In addition to configuring the dynamic behaviour using the setting time
corresponding to a first-order filter, the reactive power setting can be
determined by a maximum gradient - this means the maximum change
in the reactive power per time period.
Maximum change in the reactive power %S
change to overexcited mode
/
lim
NOTE: The gradient is overlaid with the settling time.
65,534 [% S
/
lim
1
Settling time in the event of an abrupt change in the reactive power tar-
get value (e.g. caused by a voltage jump). The transient behaviour cor-
responds to a first-order filter (PT-1) with setting time = 5 Tau.
2000 [ms]
NOTE: The settling time is overlaid with the increasing and decreasing
gradient.
In the event of a significant voltage deviation, the maximum reactive
power adjustment range can be limited by a minimum cos ϕ in order to
prevent an excessive reactive power supply and, as a result, a significant
0 /
reduction in the maximum active power that can be fed in.
Minimum cos ϕ in overexcited operating mode (in-feed).
Minimum cos ϕ in underexcited operating mode (in-feed).
Minimum cos ϕ in overexcited operating mode (charge).
Minimum cos ϕ in underexcited operating mode (charge).
P-priority can be selected as an alternative to the standard setting Q-pri-
ority. When it comes to P-priority, the reactive power adjustment range
is limited subject to the limited apparent power of the inverter and the
active power that is currently available and fed in.
Up to four characteristic curves can be configured independently and
one of them can be activated for regulation each time.
Specify the number of nodes for the Q(U) characteristic curve.
Power of the node as a percentage of the maximum power.
For the 1st node, the power must be 0%; for the last node, the power
must be 100%. The power values of the nodes must increase continu-
ously.
] /
lim
] /
0.1
lim
Voltage of the node in volts.
The voltage values of the nodes must increase continuously. At voltages
] /
below the 1st node and voltages above the last node, the reactive
lim
] /
0.1
power value of the 1st or last node is used each time.
nom
Reactive power mode Underexcited relates to inductive load, overex-
cited relates to capacitive load.
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137
Manual
/min in the event of a
lim
.
N
TL3-S