Manual
Country-
Level Display/
spec. Set-
Setting
tings
Activation threshold at
1
2
3
4
4
underfrequency
40 – 60 [Hz] /
[Hz]
Activation threshold at
overfrequency
50 – 70 [Hz]
[Hz]
Gradient on falling fre-
1
2
3
4
4
quency
0 – 200 [% Pref/
Hz] /
40 [% Pref/
Hz] /
1
Not for IL,
P(f) deactivation time
1
2
3
4
4
IT
0 – 6000000 [ms] /
0 [ms] /
P(f) deactivation gradi-
1
2
3
4
4
ent
0 – 65534 [% Smax /
min] /
P(f) intentional delay
1
2
3
4
4
0 – 5,000 [ms] /
[ms] /
Deactivation range
1
2
4
4
3
lower limit
45 – 61.5 [Hz] /
0.01 &
Deactivation range up-
per limit
45 – 70 [Hz] /
Output gradient limita-
4
1
2
3
4
tion increase & Output
gradient limitation de-
crease
1 – 65534 [% Slim /
min] /
Slim / min] /
P(f) settling time
1
2
3
4
4
200 – 2000 [ms] /
200 [ms] /
Password protection
Status
P(U)
2
1
3
4
4
Operation mode
3
1
2
4
4
Off | On
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137
TL3-S
Action in this menu/meaning
1. Set the frequency thresholds for activating the power limitation
with undervoltage.
0.01
2. Set frequency thresholds for activating the power limitation with
overvoltage.
0.01
F Specify gradient in the case of a decreasing frequency as a %
thousand) / minute (if mode "1" or mode "2" is active).
F Specify time for power reduction (if mode 1 is active).
1000 [ms]
F Determine the deactivation gradient.
10 /
1
F Set the power limitation delay.
0
1
F Set the lower and upper deactivation range in Hz.
NOTE: Only evaluated in mode 1.
The function is deactivated if the frequency returns to the range
between the minimum and maximum deactivation threshold and re-
mains in this range for the duration of the deactivation time.
0.01
F Specify the increasing and decreasing output gradient.
65534 [%
1
1. Set the P(f) settling time mode.
2. Activate optional password protection.
1 [ms]
3. Confirm the action field.
NOTE: Activate voltage-dependent power reduction via the P(U)
menu.
F Activate the control process.
Off: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to inter-
ference.
Configuration and operation | 9