9 | Configuration and operation
Country-
Level Display/
spec. Set-
Setting
tings
Monitoring 10 minute
3
1
2
4
4
average grid voltage
10 min. average
Overvoltage aver-
aging / country-de-
pendent [% Unom] /
0.1%
Island Detection
2
1
3
4
4
Mode
1
2
3
4
4
Off / ROCOF / RO-
COF enhanced / Fre-
quency shift
Password Protection
ROCOF
1
2
3
4
4
Password Protection
ROCOF enhanced
Password Protection
ROCOF threshold stage
1
2
3
4
4
1 value
[Hz / s] /
ROCOF threshold stage
2 value
[Hz / s] /
ROCOF threshold stage
1 time
[ s] /
0.1
ROCOF threshold stage
2 time
[ s] /
0.1
ROCOF enhanced
1
2
3
4
4
ROCOF threshold stage
1
2
3
4
4
1 value
[Hz / s] /
ROCOF threshold stage
2 value
[Hz / s] /
ROCOF threshold stage
1 time
[ s] /
0.1
ROCOF threshold stage
2 time
[ s] /
0.1
Page 44
Action in this menu/meaning
NOTE: Monitoring of a variation in the average voltage value of 10
minutes.
F Activate if necessary.
F Set the voltage in % via averaging.
NOTE: Grid operators require shutdown of the device with standalone
grid detection. More detailed information at: [See sec-
tion 10.5} Page 81]
NOTE: This function is active in the factory setting and may only be de-
activated in standalone islanding operation (without grid).
1. Select mode and note menu items.
2. Activate password protection if necessary.
3. Confirm the action field.
F Activate passive grid influence by application of a frequency.
F Activate active grid influence by application of a frequency.
F Define threshold for ROCOF.
0.1 – 6.0
0.1
0.1 – 6.0
0.1
F Define time value for ROCOF.
0.10 – 5.00
0.10 – 5.00
NOTE: Active detection after exceeding the first threshold.
F Define threshold for ROCOF.
0.1 – 6.0
0.1
0.1 – 6.0
0.1
F Define time value for ROCOF.
0.10 – 5.00